Enkel Boks 10 Pair is a centralized module for integrating all components in the access control system (ADK) through one 10-pair cable. The solution combines control signals and supply in one structured connection for faster installation and easier troubleshooting, without compromising performance. The product has been developed with regard to the requirements in TEK17 for doors and escape routes (including §11-13, §11-14 and §12-13), including fire override and correct configuration of locks in escape routes.

 Main features and benefits

  •  Centralized control via one 10-pair cable between ADK and door environment for reduced installation time and fewer sources of error.
  •  Standard scenarios for opening/locking from ADK (card/phone/code), with consistent time profiles.
  •  Automatic door opening via Elbow switch while the signal can be used as REX in ADK.
  •  Control and power supply of night lock (configurable).
  •  FIRE evacuation mode with priority disconnection of lock/holding magnet on escape door.
  •  Monitoring of door status, box sabotage and relevant alarm signals.
  •  Monitoring of KAC — KAC (manual fire alarm / emergency opening switch, NS-EN 54-11) — for safe evacuation.
  • Compatible with: Ruler 120140 / 120103
  • Dimensions: 104 × 90 × 18 mm
  • Cable: 10-pair (up to 100 m), standard color code
  • Operating voltage: 24 VDC ±10%, quiescent current ≈ 40 mA
  • Maximum rated current through the card's lines: up to 5 A
  • Inputs/outputs: 50 easily removable connectors for connection

Signals from ADK

  • Power supply for reader 12–24 V
  • Reader control OSDP (RS-485), Wiegand, RS-485
  • Night lock control (NC)
  • Constant 24 V auxiliary voltage
  • Fire-controlled 24 V (release in case of FIRE)
  • KAC (manual fire alarm / emergency opening switch, NS-EN 54-11), sabotage
  • Door status (alarm)
  • Main lock control NO/NC 24 V
    The choice of operating type (fail-safe / fail-secure) is set with a DIP switch. On doors in escape routes, the lock should be configured as fail-safe.
  • REX / Elbow breaker

Executive door components

  • Power supply to electromagnet to keep the door open (HOLD)
  • Night lock — power supply/control
  • Night lock control
  • Signal from external Elbow switch (mounted 0.8–1.2 m above the floor and outside the door leaf's swing area)
  • Signal from internal Elbow switch (mounted 0.8–1.2 m above floor and outside the door leaf swing area)
  • Signal from REX (mounted outside the door leaf's swing area)
  • Alarm KAC signal (manual fire alarm / emergency opening switch)
  • Emergency door opening activation signal (KAC)
  • Signal magnetic contact door
  • Signal microswitch door
  • Lock control NO/NC 24 V
  • Automatic door opener control (AUTO)

Power supply

Constant power supply (always on):

  • Night lock 24 V (not on escape doors; there the night lock is fire-controlled and is disconnected in the event of a FIRE)
  • Readers 12–24 V — separate line for independent operation of card readers
  • Backlight 24 V for lighting KAC, indicators and Elbow switch (max 300 mA total)

Fire-controlled power supply (overrides all modes):

  • Electromagnet (HOLD) disconnects in case of FIRE
  • Night lock 24 V is deactivated/disconnected in the escape route (minus can be connected via KAC if necessary)
  • Main lock 24 V disconnected for fail-safe opening in escape route
  • FIRE overrides lock in escape route: power is disconnected for fail-safe opening; night override

Security and reliability

  • Short circuit protection: 300 mA fuses for Elbow Switch buttons and backlight (isolated from mains lock voltage)
  • Isolation of emergency power circuits to prevent short circuit effects
  • Tamper control: signal in case of unauthorized access to the box