Interactive model: Enkel Boks 6 Par

Try Enkel Boks 6 Par yourself: see what happens to the lock, hold-open magnet, night lock and door operator with a card, in a fire, at night and on emergency release.

Enkel boks 6 par Relay logic · K1–K5 · terminals 1–40

Without JavaScript the model shows its default state and the controls do not work. The ‘Scenarios’ table further down shows the state for each scenario.

Controls

From access control

At the door

Installation

The board does not change: 21 carries +24 V while K5 is off, 23 while K5 is on. This choice says where the lock is wired. Fail-safe is locked with power, fail-secure is locked without power. The difference shows on fire and KAC.

← Swipe to see the whole diagram →

Wiring diagram for Enkel Boks 6 ParTerminals 1 to 20 are on the left and 21 to 40 on the right, with relays K1 to K5 in the middle. Lines carrying current are orange; the legend is below the diagram. The state is written out in the ‘State’ table and in the text below it.ENKEL BOKS 6 PARF1 300 mAF2 300 mA−24−24+24ELK1 Fire (V23079). Coil: terminal 8 → board 0 V. Contacts 4·9 → 5·8 give +24 V to the lock (via K5) and hold magnet 40.K1 FIRE5·8 NO4·9 C3·10 NC1+12−D1K2 Fire/AGA. Coil is fed from the fire line through K5 contact 21→22. Set 1 drives night lock 38–39, set 2 gates the outdoor elbow switch (32 → 35).K2 FIRE/AGA3 NC4 C5 NO10 NC9 C8 NO1+12−K3 Night lock. Coil straight from terminal 10. Parallel with K2 in loop 38–39: both must be energised to lock the night lock.K3 NIGHT3·10 NC4·9 C5·8 NO1+12−D3K4 REX. Coil sits on +24 V via F2 and pulls in when elbow switch 19–20 connects its minus to −24 V via F1. Set 1: REX to ACS (6 → 5). Set 2: door operator (35 → 34).K4 REX10 NC9 C8 NO3 NC4 C5 NO1+12−D4K5 Lock (Schrack RT42). Coil: terminal 9. Set 11/12/14 moves +24 V between 21 (NC) and 23 (NO). Set 21/22 cuts the coil of K2.K5 LOCK22 NC21 C24 NO14 NO11 C12 NCA1+A2−D21−24 V constant2−24 V constant3+24 V constant4+24 V constant5GND (ACS)6REX → ACS7Alarm8Fire9Lock10Night lock11Reader data ↔ 1312OSDP ↔ 1413D0 / TR−14D1 / TR+15Card reader −16Card reader +17REX button18REX button19Indoor elbow20Indoor elbow40+24 V hold magnet39Night lock control38Night lock control37+24 V to night lock360 V35Door operator34Door operator33Outdoor elbow32Outdoor elbow31KAC relay 130KAC relay 129KAC relay 228KAC relay 227Door magnetic contact26Door magnetic contact25Door microswitch24Door microswitch23+24 V EL (NO)220 V EL21+24 V EL (NC)
  • live / closed circuit
  • path ready: K2 released, outdoor switch armed
  • ±24 V supply
  • de-energised / open
  • external device
  • alarm (v2)

State

NORMAL
K1 energised
K2 energised
K3 dropped
K4 dropped
K5 dropped
EL-LOCKLOCKED
Night lockRELEASED
Hold magnet 40HOLDING
Door operator 34–35—
REX to ACS 5–6—
Outdoor switchblocked
Doorclosed
Door + operator
EL-LOCK
Night lock
Hold magnet · fire-controlled (40)
Card reader
Outdoor elbow
Door is locked. K1 and K2 are energised. The outdoor elbow switch is blocked by K2. A card or REX opens the door.

Interactive model of the Enkel boks 6 par relay logic. Patent pending. © Teren AS

Scenarios

What the box does in each scenario, calculated by the same relay logic as the model above. A relay is energised when its coil is powered.

ScenarioInputModeEnergised relaysLock on 21 (NC, fail-safe)Lock on 23 (NO, fail-secure)Night lockHold magnet 40Door operator 34–35Outdoor switch
NormalNo button pressedNORMALK1 K2LOCKEDLOCKEDRELEASEDHOLDING—blocked
CardCard / Lock (terminal 9)ACCESS GRANTEDK1 K5RELEASEDRELEASEDRELEASEDHOLDING—enabled
REX exitREX exit button (17–18). ACS answered REX: Lock signal on terminal 9 (same as a card)ACCESS GRANTEDK1 K5RELEASEDRELEASEDRELEASEDHOLDING—enabled
Indoor elbowIndoor elbow switch (19–20). ACS answered REX: Lock signal on terminal 9 (same as a card)ACCESS GRANTEDK1 K4 K5RELEASEDRELEASEDRELEASEDHOLDINGCOMMANDenabled
Outdoor elbowOutdoor elbow switch (32–33)NORMALK1 K2LOCKEDLOCKEDRELEASEDHOLDING—blocked
Card + outdoorCard / Lock (terminal 9) and outdoor elbow switch (32–33)ACCESS GRANTEDK1 K5RELEASEDRELEASEDRELEASEDHOLDINGCOMMANDenabled
Night lockNight lock on (terminal 10)NIGHT LOCKK1 K2 K3LOCKEDLOCKEDLOCKEDHOLDING—blocked
FIRENo power on terminal 8FIRE—RELEASEDLOCKEDRELEASEDRELEASED—enabled
KAC releaseKAC emergency release pressed (30–31)KAC RELEASE—RELEASEDLOCKEDRELEASEDRELEASED—enabled

Relays K1–K5

  • K1 Fire (V23079). Coil: terminal 8 → board 0 V. Contacts 4·9 → 5·8 give +24 V to the lock (via K5) and hold magnet 40.
  • K2 Fire/AGA. Coil is fed from the fire line through K5 contact 21→22. Set 1 drives night lock 38–39, set 2 gates the outdoor elbow switch (32 → 35).
  • K3 Night lock. Coil straight from terminal 10. Parallel with K2 in loop 38–39: both must be energised to lock the night lock.
  • K4 REX. Coil sits on +24 V via F2 and pulls in when elbow switch 19–20 connects its minus to −24 V via F1. Set 1: REX to ACS (6 → 5). Set 2: door operator (35 → 34).
  • K5 Lock (Schrack RT42). Coil: terminal 9. Set 11/12/14 moves +24 V between 21 (NC) and 23 (NO). Set 21/22 cuts the coil of K2.

Modes

NORMAL

Door is locked. K1 and K2 are energised. The outdoor elbow switch is blocked by K2. A card or REX opens the door.

ACCESS GRANTED

Lock signal on terminal 9: K5 energised and moved +24 V from 21 to 23. K5 also cut the coil supply of K2, so K2 dropped — the outdoor elbow switch works and the night lock is released.

REX does not touch K2 — the button only reaches the ACS on 5–6. The ACS answered with the Lock signal on terminal 9, the same output as for a card. So K5 pulled in, K2 dropped, and the outdoor elbow switch is enabled while the signal lasts.

NIGHT LOCK

Night lock: K3 and K2 are both energised, so loop 38–39 is open and the night lock is locked. A card drops K2 and so releases the night lock.

FIRE

Fire: terminal 8 is dead. K1 dropped and removed +24 V from the lock and the hold magnet. K2 dropped too, so both elbow switches open the door and the night lock is released. K3 stays energised — that is correct, K2 alone releases the night lock.

The model shows a night lock on constant 24 V (terminal 37). On exterior doors that must stay locked during fire, the night lock is fed from fire-controlled 24 V (terminal 40): it then stays locked, and the door is opened mechanically.

KAC RELEASE

KAC emergency release: loop 30–31 is open and the board's 0 V is gone. K1, K2, K3 and K5 drop together and the lock loses its return on 22. The indoor elbow switch still works, because K4 returns through 19–20.

The model shows a night lock on constant 24 V (terminal 37). If the night lock is fed from fire-controlled 24 V (terminal 40), it also stays locked on KAC.

NO POWER

No power on terminals 1–4. All relays dropped.

A fail-secure lock on 23 gets no power on fire or KAC and stays locked. Use 21 for escape doors.