Enkel Boks + INTEGRA

Wiring diagram for Enkel Boks and INTEGRA S-Node G2, with the door node at the door and its own 6-pair cable between the node and the box.

INTEGRA S-Node G2 – door node at the door

Enkel Boks 6 ParController at the doorVersion V2.1 Draft

Draft: some points of the diagram are not confirmed yet and are marked «sjekk» in the PDF. Check before installation.

The INTEGRA S-Node G2 (door and alarm node for Moveo / Moveo XL) sits at the door and gets 24 V and LON from the INTEGRA system, not from Enkel Boks. The central cabinet cable provides power (1–4) and fire (8), and a separate 6-pair cable runs between the S-Node and the box; DO1 gives +24 V on terminal 9, and DO2 controls the night lock on terminal 10 per schedule in Moveo. The terminal names are taken from the wiring picture for the previous node generation (AP-Node, same board layout) and must be confirmed against the S-Node G2 manual before installation.

Download wiring diagram (in Norwegian): INTEGRA S-Node G2 – door node at the door (PDF)

Page 1 of the wiring diagram for Enkel Boks and INTEGRA S-Node G2 – door node at the door
  • Lock: S-Node G2 DO1 (terminal 1) → terminal 9 (Black/grey, pair 5); DO1 (terminal 2) ← terminal 12 (White, pair 6, +24 V via bridge 14 → 16 and F2). The jumpers on «normal opened contact», not «active output».
  • Night lock: DO2 (terminal 2) → terminal 10 (Grey, pair 5), with red bridge DO1 terminal 2 → DO2 terminal 1. Moveo keeps DO2 energised all night (not pulsed); one DO per door, no parallel connection of 10.
  • Inputs: 5 (Black/green, pair 3) → DI2 common with bridge to DI3 common; 6 (Green, pair 3) → DI3 (REX); 7 (Black/brown, pair 4) → DI2 (door status). Digital (unbalanced) without EOL as standard.
  • Reader: INTEGRA reader directly on the S-Node's reader terminal (RS-485 and 24 V DC), termination on the node and the last reader; not via Enkel Boks.
  • Power: S-Node 24 V DC (20–30 V) from the INTEGRA system with battery backup. Common 0 V with the box's power supply is not needed, because only potential-free contacts run between them.
  • Cables: central cabinet cable 6 PAR 0,6 PT HF max 100 m (pair 1, pair 2, Brown pair 4); S-Node–box 6 PAR 0,6 PT HF (pair 3, Black/brown pair 4, pair 5, White pair 6).
  • In a classified system (SSF 1014) it must be clarified that door contact via Enkel Boks 7–5 is accepted.
Connection table (cable journal)

Cables

  • 6 PAR 0,6 PT HF (max 100 m): Central cabinet (power supply 24 V, fire relay) ↔ Enkel Boks. Used: pair 1, pair 2, brown (pair 4)
  • 6 PAR 0,6 PT HF: S-Node G2 (at the door) ↔ Enkel Boks. Used: pair 3, black/brown (pair 4), pair 5, white (pair 6)
  • In the central cabinet: Red bridge from the power supply to the fire relay
  • Bridges: On S-Node (DI2/DI3 common, DO1 → DO2 +24 V) and in Enkel Boks (14 → 16: terminal 12 gets +24 V)
  • Reader cable (INTEGRA): S-Node G2 RS-485 + 24 V DC ↔ INTEGRA card reader (does not go via Enkel Boks)

One row = one conductor: terminal in Enkel Boks → conductor → where it goes. The tables are translated from the PDF, which is in Norwegian; the PDF is the document to install from.

TerminalFunctionConductorConnects toNote
1−24 V constantBlack/blue (pair 1)Power supply 0 V (−)
2−24 V constantBlue (pair 1)Power supply 0 V (−)
3+24 V constantBlack/or. (pair 2)Power supply +24 V
4+24 V constantOrange (pair 2)Power supply +24 V
8FireBrown (pair 4)Fire relay NC (C = +24 V)+24 V = normal. Fire: the voltage drops out.
5GND to S-NodeBlack/green (pair 3)S-Node G2 DI2 commonCommon for REX (5–6) and door status (7–5). Black bridge DI2 common → DI3 common on S-Node. Common terminal in the pair: check.
6REX to S-NodeGreen (pair 3)S-Node G2 DI3Potential-free NO in Enkel Boks (5–6). DI3 = inside push button (factory, AP-Node).
7Alarm (door status)Black/brown (pair 4)S-Node G2 DI2NC loop (closed = door closed). DI2 = magnetic contact (factory, AP-Node). Balancing: check.
9Lock (open)Black/grey (pair 5)S-Node G2 DO1 (terminal 1)DO1 with jumpers on «normal opened contact» (dry contact), not «active output».
10Night lockGrey (pair 5)S-Node G2 DO2 (terminal 2)+24 V = night mode. Moveo controls DO2 by schedule, held all night (not a pulse). Jumpers on «normal opened contact».
12+24 V to S-Node relayWhite (pair 6)S-Node G2 DO1 (terminal 2)+24 V from 16 (F2) via bridge 14 → 16 (12 ↔ 14 straight through), red bridge on to DO2. No reader on 13–14.
–+24 V to fire relayRedPower supply +24 V → fire relay CNo time relay: night lock from DO2.
–Common DI2/DI3Black (bridge)S-Node DI3 common → DI2 common (terminal 5)Common terminal in the pair: check against the manual.
–+24 V to DO2Red (bridge)S-Node DO1 terminal 2 → DO2 terminal 1DO1 and DO2 as dry contacts to the same +24 V.
14+24 V to 12RedEnkel Boks terminal 16 (+24 V via F2)Bridge 14 → 16 in the box. 12 ↔ 14 is straight through, so 12 gets +24 V.
–Reader RS-485 + 24 Vper INTEGRAS-Node 4-pole reader terminal → INTEGRA card reader2 × RS-485 (A, B) + 2 × 24 V DC. Order: check. Termination on S-Node and the last reader.

In the central

  • No time relay: night lock from DO2 (schedule in Moveo). S-Node gets 24 V and LON from INTEGRA (not drawn); no common 0 V with the power supply. 11 and 13 are not used. 15–16 supply the door side as usual (lights in elbow switches and emergency release/KAC box), and bridge 14 → 16 gives +24 V on 12.

The door side (21–40 and 17–20) is the same for all brands – see the drawing, page 1.

Controller setup and DIP in Enkel Boks
SettingFactoryUsed asStatus
DO1 / DO2 (2 terminals each)Jumpers per relay: «normal opened contact» or «active output»; a separate jumper selects the power source for the relay output (AP-Node picture)«normal opened contact»: DO1 dry NO 9 ↔ 12 (+24 V), DO2 dry NO 10 ↔ +24 V (red bridge from DO1). Position of the jumpers on G2: checkCheck
DO2 scheduleRelays are controlled from MoveoNight lock: DO2 energises per schedule and holds all night (not pulse). On power failure at S-Node the night lock drops out: check that this is wantedCheck
Relay rating1 A (datasheet p. 2)Drives only coil K5 in Enkel Boks: good marginOK
DI2 / DI3DI1 lock contact, DI2 magnetic contact, DI3 inside push button (AP-Node); single/double/triple balancedDI2 = door status from 7–5 (NC), DI3 = REX from 5–6 (NO), DI1 not in use. Digital or EOL resistors: checkCheck
Reader terminal (4-pole)RS-485 + 24 V DC to readers; termination at the node and the last readerINTEGRA reader directly on S-Node, not via Enkel BoksOK
Power and LON24 V DC (20–30 V), 45–110 mA; LON FTT-10 to MoveoFrom the INTEGRA system (battery backup per SSF 1014). Not from Enkel BoksCheck
Terminal nameNot in the public datasheetTaken from the AP-Node image (same board). Confirm with the S-Node G2 manualCheck
CertificationSSF 1014 ed. 5, alarm class 3Door contact via Enkel Boks 7–5: check that this is accepted in a classified systemCheck
Multiple doors4 relays (DO1–DO4), 8 inputsDoor 2 = DO3 (lock) + DO4 (night lock) + DI5/DI6 (check) to its own Enkel Boks; each door has its own night lock DOCheck
DIPFunctionSuggestion for this setup
S2.1TamperON (tamper in the box not connected)
S2.2Emergency release, relay 2 (KAC)OFF when an emergency release (KAC box) is connected to 28–29
S2.3EOL resistor R2ON (DI2 digital without EOL); OFF only when R2 is fitted because the installation requires EOL
S2.4Magnetic door contact and microswitchOFF when MKT is connected to 26–27
S2.5Door microswitchOFF when a microswitch is connected to 24–25
S2.6Fire – manual modeOFF when a fire relay is connected to terminal 8
S2.7Night lock – manual modeOFF when the night lock is controlled from terminal 10
S2.8Emergency release, relay 1 (KAC)OFF when an emergency release (KAC box) is connected to 30–31