Contact us

Back to Enkel Boks

Enkel Boks + RCO

Wiring diagram for Enkel Boks and RCO R-CARD M5 DB-50 Gen2, with the door controller in the central cabinet and one 6-pair cable to the door.

RCO R-CARD M5 DB-50 Gen2 – controller in the central cabinet

Enkel Boks 6 ParController in the central cabinetVersion V2.1

The RCO R-CARD M5 DB-50 Gen2 sits in the central cabinet, and one 6-pair cable with all 12 conductors runs to Enkel Boks. DOOR RELAY (jumper P8 changed to potential-free NO) gives +24 V on terminal 9, the night lock is controlled by the time relay in the central cabinet, and the RCO reader sits on 13–16 with RS-485 through pair 6 and 24 V from the box. The DB-50 gets power and bus from the UC-50 Gen2, which runs on the same power supply as Enkel Boks.

Download wiring diagram (in Norwegian): RCO R-CARD M5 DB-50 Gen2 – controller in the central cabinet (PDF)

Page 1 of the wiring diagram for Enkel Boks and RCO R-CARD M5 DB-50 Gen2 – controller in the central cabinet
  • Lock: DB-50 P4/14 DOOR RELAY b → terminal 9 (Black/grey, pair 5); P4/13 a gets +24 V from the power supply via time relay C and fire relay C (red chain). Jumper P8 is changed from «Matande NO» (factory) to potential-free NO.
  • Inputs: 5 (Black/green, pair 3) → DB-50 P5/18 (+5 V) with bridge P5/18 ↔ P5/20; 6 (Green, pair 3) → P5/17 EXIT BUTTON (NO); 7 (Black/brown, pair 4) → P5/19 DOOR SENSE (NC = door closed). Unbalanced.
  • Reader bus: P19/98 RS485 A → terminal 11 → 13, P19/99 RS485 B → 12 → 14; jumper P13 = RS-485 (P19). Max 100 m through pair 6.
  • Reader: RCO reader for 12–24 V on 13–16 with 24 V from the box; the model is chosen per site.
  • Power: the DB-50 gets 18–30 V DC from the local bus (P7) from the UC-50 Gen2. The UC-50 runs on the same power supply as Enkel Boks, so common 0 V follows from a single power supply.
  • Night lock: time relay NO → Grey (pair 5) → terminal 10.
  • DOOR RELAY tolerates max 1 A at 24 V DC and controls only the coil in the box.
Connection table (cable journal)

Cables

  • 6 PAR 0,6 PT HF (max 100 m): Central cabinet (DB-50 Gen2, power supply, fire relay, time relay) ↔ Enkel Boks
  • In the central cabinet: Bridges and RCO bus in the cabinet
  • Reader at the door: Enkel Boks 13–16 ↔ RCO reader (RS-485 terminal bus, through pair 6)

One row = one conductor: terminal in Enkel Boks → conductor → where it goes. The tables are translated from the PDF, which is in Norwegian; the PDF is the document to install from.

TerminalFunctionConductorConnects toNote
1−24 V constantBlack/blue (pair 1)Power supply 0 V (−)
2−24 V constantBlue (pair 1)Power supply 0 V (−)
3+24 V constantBlack/or. (pair 2)Power supply +24 V
4+24 V constantOrange (pair 2)Power supply +24 V
5Common to RCOBlack/green (pair 3)DB-50 P5/18 (EXIT BUTTON, +5 V)Bridge P5/18 ↔ P5/20 on DB-50: same common point for REX and door status.
6REX to RCOGreen (pair 3)DB-50 P5/17 EXIT BUTTONFactory: NO, unbalanced. Potential-free contact in Enkel Boks (5–6).
7Alarm (door status)Black/brown (pair 4)DB-50 P5/19 DOOR SENSEFactory: NC = door closed, unbalanced.
8FireBrown (pair 4)Fire relay NC (C = +24 V)+24 V = normal. Fire: the voltage drops out.
9Lock (open)Black/grey (pair 5)DB-50 P4/14 DOOR RELAY bJumper P8 is changed from «Matande NO» (factory) to potential-free NO. P4/13 a gets +24 V from the power supply via time relay C and fire relay C.
10Night lock (central)Grey (pair 5)Time relay NO (C = +24 V)+24 V = night mode. Alternative: DB-50 SIREN P4/16 (see setup).
11Reader bus A → 13Blue/white (pair 6)DB-50 P19/98 RS485 AStraight through 11 → 13 in the box. Jumper P13 = RS-485 (P19).
12Reader bus B → 14White (pair 6)DB-50 P19/99 RS485 BStraight through 12 → 14 in the box.
–+24 V to lock relayRedPower supply +24 V (via time relay C and fire relay C) → DB-50 P4/13 aRed chain: power supply +24 V → time relay C → fire relay C → P4/13.
–Common 0 V reader busBlackPower supply 0 V → DB-50 P19/97 (24VDC −)Dashed stub on the drawing, marked «Common 0 V: UC-50 on the same power supply». UC-50 is on the same power supply as Enkel Boks, so common 0 V follows from one power supply. If UC-50 gets its own power supply, connect P19/97 to 0 V on the box's power supply with a solid conductor «common 0 V – required».
–Local bus from UC-50RCO cableDB-50 P7: 29 a(+), 30 b(−), 31 A, 32 BPower 18–30 V and RS-485 from UC-50 Gen2 P2/5–8. SW2 = address, SW3 = termination on the last unit.
13Reader RS485 Aper readerRCO reader A
14Reader RS485 Bper readerRCO reader B
15Reader −per readerRCO reader 24 V −−24 V via F1 300 mA.
16Reader +per readerRCO reader 24 V ++24 V via F2 300 mA. Only an RCO reader for 12–24 V.

In the central

  • Red bridge in the central cabinet: power supply +24 V → time relay C → fire relay C → DB-50 P4/13.
  • All 12 conductors in the 6-pair cable are in use: pair k goes to terminal 2k−1 (black/striped) and 2k (colour), as on the Axis drawing.

The door side (21–40 and 17–20) is the same for all brands – see the drawing, page 1.

Controller setup and DIP in Enkel Boks
SettingFactoryUsed asStatus
P8 DOOR RELAYPowered NO (outputs DB-50 voltage)Potential-free NO, +24 V from the power supply in on 13Must be changed
P13 terminal busRS-485 (P19) – listed as supplied in the guideReader via pair 6 to the door. RS-485 to the reader through pair 6: max 100 mOK
EXIT BUTTON 17–18NO, unbalanced, requires a potential-free contactREX from terminal 5–6OK
DOOR SENSE 19–20NC = door closed, unbalancedAlarm from terminal 7–5OK
SIREN 15–16 (optional)Powered NO, common alarmIndividual night lock: P11 potential-free NO + «Day/night locking» in R-CARD M5Must be changed
RelayMax 1 A at 24 V DC (PTC 1 A)Drives coils in Enkel BoksOK
Power18–30 V DC from the local bus (PTC 500 mA)From UC-50 Gen2OK
DIPFunctionSuggestion for this setup
S2.6Fire – manual modeOFF when a fire relay is connected to terminal 8
S2.7Night lock – manual modeOFF when the night lock is controlled from terminal 10
S2.8Emergency release, relay 1 (KAC)OFF when an emergency release (KAC box) is connected to 30–31